Electrical distribution method for improving the quality of landscape lighting engineering

1, outdoor cable selection problem
52 luminaire wiring using indoor BV wires
Figure 6-1 Luminaire wiring using indoor BV wires
Problem: Use BV cable or rubber cable as the lamp power cable. The cable rubber sleeve is susceptible to heat aging or melting and bonding, forming a short circuit or leakage, which has potential safety hazards.
Requirements: All outdoor lighting pipelines must be YJV or YJV22. The underwater light leads and submersible pump motors must use JHS underwater cables. The outdoor lighting leads can be RVV (as shown in Figure 6-2). Wires replace outdoor cables.
53 cable
Figure 6-2 AYJV cable
54 submersible pump and submarine lamp dedicated JHS cable
B submersible pump and JHS cable for underwater lights
55 outdoor lighting lead RVV cable
C outdoor lamp lead RVV cable
The outdoor cable protection pipe shall be steel pipe, PE pipe or PVC pipe (heavy duty). It shall not be directly buried with KBG pipe or cable (except YJV22). The pipeline depth shall be less than 0.5m. When passing the road and over the wall, additional steel pipe protection is required. .
2. Distribution control system
56 control loop excessive lighting system
Figure 6-3 Excessive lighting system for the control loop
Problem: For each circuit of the luminaire, the contactor is controlled and the switch is controlled in time to form too many control loops and control modes. Not only raises the cost of equipment, but also does not facilitate the unified management of the property.
Requirement: According to the control mode requirements, it can be divided into full-open (major festival), partial full-open (festival or weekend), functional opening (the first half of the week), and energy-saving mode (after midnight). Set two to three control modes according to the actual situation. Manual control and timely control, if necessary, increase the light control function. Load two to four time-controlled switches on the control loop and set the corresponding switch time. In order to facilitate the property management personnel to achieve the required opening and closing function with fewer buttons and timely control.
For indoor installation, the control section (or distribution control integrated into a cabinet) is best placed in the guard duty room. The small distribution box is installed on the wall. If the wall is mounted on the duty room, it is recommended to make a wardrobe room to conceal the power distribution box. Large distribution boxes can be installed on the floor. Place indoor corners.
57 small distribution box set in the concealed treatment of the duty room
Figure 6-4 Concealed handling of a small distribution box set in the duty room
Large cabinet floor installation
For outdoor installation, it is recommended that the concealed installation or the outer casing be processed into a harmonious color of the landscape. It is not easy to directly expose the stainless steel box to the landscape surface, which affects the look and feel.
58 stainless steel case exposed in the landscape
Figure 6-5 Stainless steel case exposed to the outside of the landscape
It is recommended to handle the color coordinated with the landscape (not for glass doors)

Lighting control points and responsibilities